Schneider Electric LC1D80M7C Original Industrial Spare TeSys D
LC1D80M7COriginal Schneider Electric LC1D80M7C TeSys D 80A AC contactor. Industrial spare for motor control panels. 12-month warranty. Fast global shipping from TOPNLMS.
Request availability, condition, lead time and export shipping details for LC1D12BDC.
Send this exact part number, quantity and destination country. TOPNLMS will confirm availability, condition and export lead time before quotation.
The Schneider Electric LC1D12BDC is a 24VDC coil designed for the TeSys D series contactor platform — one of the most widely deployed motor control components in global industrial automation. Whether you are managing a scheduled maintenance window, responding to an unplanned shutdown, or building a strategic spare parts inventory for aging control systems, the LC1D12BDC delivers the electrical reliability and dimensional compatibility that maintenance engineers depend on.
In factory environments where motor starters, pump control panels, HVAC drive cabinets, and conveyor systems rely on TeSys D contactors, coil degradation is one of the most common causes of unexpected downtime. A worn or failed coil produces erratic pull-in behavior, audible chattering, or complete failure to energize — all of which can cascade into production losses far exceeding the cost of a replacement coil. Stocking the LC1D12BDC as a verified original spare eliminates this risk and restores system confidence within minutes of a fault diagnosis.
| Parameter | Specification |
|---|---|
| Part Number / SKU | LC1D12BDC |
| Brand | Schneider Electric |
| Series | TeSys D |
| Component Type | Contactor Coil (Replacement) |
| Coil Voltage | 24V DC |
| Compatible Contactor Frame | LC1D09 / LC1D12 / LC1D18 / LC1D25 (TeSys D Series) |
| Rated Current (Contactor) | 12A (AC-3, 400V) |
| Coil Power Consumption | Approx. 5.5W (holding), 70VA (inrush) |
| Mounting | Snap-fit replacement into TeSys D contactor body |
| Operating Temperature | -5°C to +60°C |
| Degree of Protection | IP20 (within enclosure) |
| Standards Compliance | IEC 60947-4-1, CE Marked |
| Country of Origin | France |
| Weight | Approx. 500g (packaged) |
| Warranty | 12 Months from date of shipment |
Experienced maintenance teams know that a contactor coil failure rarely occurs in isolation. When the LC1D12BDC is flagged for replacement during a routine inspection or post-fault analysis, it is best practice to conduct a broader assessment of the surrounding control circuit to prevent repeat failures and reduce the frequency of future interventions.
Begin by inspecting the LC1D12 contactor body itself — check the main contact tips for wear, pitting, or carbon deposits that indicate high switching cycles. If the contacts show significant erosion, replacing the full contactor assembly alongside the coil is more cost-effective than a coil-only swap. At the same time, verify the condition of the auxiliary contact blocks (such as the LA1DN11 or LA1DK11) mounted on the contactor, as these are frequently overlooked during coil-focused maintenance and can cause intermittent control signal faults.
Move upstream to the control power supply feeding the 24VDC coil circuit. Voltage instability or ripple from an aging PHASEO ABL8 series power supply is a known contributor to premature coil failure and chattering. A quick voltage measurement under load will confirm whether the supply is within tolerance. If the cabinet also houses a TeSys GV2 or GV3 motor circuit breaker, inspect its thermal trip calibration and reset mechanism — these components share the same maintenance interval as the contactor in most motor starter assemblies.
For systems using Modicon M340 or M580 PLC platforms to control the contactor via discrete output modules, verify that the output channel driving the coil is not showing leakage current or voltage drop that could cause false energization. Check the BMX DDO or BMX DRA output module terminal connections for looseness or oxidation. Loose terminals in the 24VDC control wiring are a leading cause of intermittent coil behavior that is often misdiagnosed as a coil defect.
If the installation includes Zelio Logic smart relays or Zelio Time SR2 series timing relays in the same control circuit, inspect their output contacts and verify timing parameters have not drifted. In older installations, Preventa XPS safety relay modules in the emergency stop circuit should also be tested for response time and contact integrity during the same maintenance window. Finally, review the condition of the terminal blocks (Linergy or Linergy DS series) on the DIN rail — corroded or loose terminals in the coil supply circuit are a silent cause of intermittent contactor operation that is easily corrected during a planned outage.
The LC1D12BDC is a direct field-replaceable coil for the TeSys D contactor family. Its snap-fit design allows a trained technician to complete a coil swap in under five minutes without removing the contactor from the DIN rail or disconnecting the main power cables — a significant advantage during time-critical maintenance windows where minimizing downtime is the primary objective.
For facilities managing legacy systems originally commissioned with older TeSys D contactors, the LC1D12BDC provides a fully compatible upgrade path. The coil is dimensionally and electrically identical to earlier production variants, ensuring that no control circuit modifications are required. This backward compatibility is particularly valuable in industries such as water treatment, food processing, and discrete manufacturing, where control panel redesigns are costly and disruptive.
Procurement teams managing multi-site operations are encouraged to standardize on the LC1D12BDC as a common spare across all facilities using TeSys D 12A contactors. Centralized stocking of this coil, combined with a documented replacement procedure, reduces mean time to repair (MTTR) and supports ISO 55001 asset management compliance. Each unit shipped from TOPNLMS is tested prior to dispatch and covered by a 12-month warranty, providing procurement confidence for both emergency and planned replacement scenarios.
Q1: Is the LC1D12BDC compatible with all TeSys D 12A contactors regardless of production date?
A: Yes. The LC1D12BDC coil is designed for the TeSys D frame and is compatible with LC1D12 contactors across production generations. The snap-fit coil interface has remained consistent throughout the TeSys D product lifecycle. If you are uncertain about compatibility with a specific serial number or production batch, contact our technical team with the contactor nameplate data for confirmation.
Q2: What pre-shipment testing is performed on each LC1D12BDC unit?
A: Every LC1D12BDC unit undergoes electrical continuity verification, coil resistance measurement, and insulation integrity testing before shipment. Units that do not meet Schneider Electric’s original specification tolerances are rejected. A test report is available upon request for quality-critical procurement processes.
Q3: How should the LC1D12BDC be stored as a long-term spare?
A: Store in original packaging in a dry environment between -25°C and +70°C with relative humidity below 95% non-condensing. Avoid proximity to strong magnetic fields or corrosive atmospheres. Under these conditions, shelf life exceeds five years without performance degradation. Rotate stock on a first-in, first-out basis and inspect packaging integrity annually.
Q4: What is covered under the 12-month warranty?
A: The 12-month warranty covers manufacturing defects, premature coil failure under normal operating conditions, and electrical parameter deviations from specification. It does not cover damage resulting from incorrect installation, overvoltage events, or operation outside the rated environmental conditions. Warranty claims are processed with return merchandise authorization (RMA) and typically resolved within 10 business days.
Click Quote This Model and the Part Number field will auto-fill with LC1D12BDC.